Question
Hello! Can refrigerant receivers operate on R 410A refrigerant?

Hello!

         Vessels, manufactured under the trademark FP certified in accordance with the requirements of TR CU 032/2013 and are designed to work with refrigerants - working media group 2 in accordance with the classification of TR CU 032/2013. And as Freon R-410A refer to this group, and all the vessels and apparatus TM FP can be used with R-410A refrigerant within the parameters of allowable operating pressures. The design pressure for the standard range of vessels and apparatuses TM FP is 2.8 MPa.
         Please note that the estimated value of the pressure can not be less than the maximum allowable pressure. If you design refrigeration unit with single-stage compression cycle, single-stage throttling and air-cooled condenser, when used as a refrigerant R-410A is necessary to take the calculated value of the maximum pressure a refrigerant receiver is not less than 3.8 MPa (38 bar).
         For such pressures, our factory produces special series of vessels and safety valves, initially designed for the operating pressure of 4.5 MPa (45 bar) and this is a worldwide practice, the use of receptacles with a working pressure of 4.5 MPa for refrigerants R-410A and of CO2 (subcritical. ) .Such vascular model (and more information) you can ask our distributors or directly to the factory.
        

Answer
Hello! Can refrigerant receivers operate on R 410A refrigerant?

Hello!

         Vessels, manufactured under the trademark FP certified in accordance with the requirements of TR CU 032/2013 and are designed to work with refrigerants - working media group 2 in accordance with the classification of TR CU 032/2013. And as Freon R-410A refer to this group, and all the vessels and apparatus TM FP can be used with R-410A refrigerant within the parameters of allowable operating pressures. The design pressure for the standard range of vessels and apparatuses TM FP is 2.8 MPa.
         Please note that the estimated value of the pressure can not be less than the maximum allowable pressure. If you design refrigeration unit with single-stage compression cycle, single-stage throttling and air-cooled condenser, when used as a refrigerant R-410A is necessary to take the calculated value of the maximum pressure a refrigerant receiver is not less than 3.8 MPa (38 bar).
         For such pressures, our factory produces special series of vessels and safety valves, initially designed for the operating pressure of 4.5 MPa (45 bar) and this is a worldwide practice, the use of receptacles with a working pressure of 4.5 MPa for refrigerants R-410A and of CO2 (subcritical. ) .Such vascular model (and more information) you can ask our distributors or directly to the factory.
        